KEN KIRSCHENBAUM, ESQ
ALARM - SECURITY INDUSTRY LEGAL EMAIL NEWSLETTER / THE ALARM EXCHANGE
You can read all of our articles on our website. Having trouble getting our emails?   Change your spam controls and white list ken@kirschenbaumesq.com 

******************************
More on Not to code wireless fire alarm

August 19,  2021
********************
More on Not to code wireless fire alarm from August 9, 2021 article
********************
Ken,
          It has been a while since I have chimed in on a topic.
          I think that as an industry, we still have those that struggle to understand when a fire alarm system is required.
          1. NFPA 72 doesn't tell us when a system is required, but how the part's and various pieces are to be installed; i.e. the cookbook if you will.
          2. The "menu" if you will is the adopted Code for the Jurisdiction; most typically an amended version of the IBC or NFPA 5000.  As the IBC is the most widely adopted, my examples will be taken from that.
          3. The Model IBC typically uses occupant load as the determiner in Section 907.2 (R Use Groups are a notable exception) to determine if a "manual fire alarm system" is required.  This does not typically imply smoke detection other than those required by NFPA 72 at each FACU. Areas of a building that can "drive" smoke detection are HVAC units & fire/smoke dampers, elevators, and fire/smoke doors/curtains.  When smoke detection is not required, but the Owner or Architect determines that it desired, NFPA 72 offers the option of Non-required Coverage (17.5.3.3) which only relieves the spacing requirement for the detection:
          "17.5.3.3.1 Detection installed for reasons of achieving specific fire safety objectives, but not  required by any laws, codes, or standards, shall meet all of the requirements of this Code, with  the exception of the prescriptive spacing criteria of Chapter 17."
          Notably, NFPA 72 doesn't relieve any spacing (CD) or output (DBA) for notification devices when they are not required, but being voluntarily installed.  Basically notification is an all or nothing option as the Code exist today.
          Some AHJ's seem to take the tack of having their own unwritten Code for this application.  As an example, I know of a CA AHJ that is requiring a single LF sounder/strobe in the common area of each R-2 apartment when the CA Code doesn't require interior notification.  My course of action to ensure that this is being noted correctly on the permit drawings is to state: "NOTIFICATION DEVICE PLACEMENT PER STATED REQUIRMENTS OF ____________ FIRE MARSHAL."  If the AHJ approves the permit drawings; then we are one step forward along on the process.  If the installing company then tailors their contract language (by working with you of course), I think that the risk has been mitigated.  Your and others thoughts?
  Thanks.                    
Dave Miller, SET, Principal
MCG Design Services
 Direct:503-537-9200
dave@mcg-design.net 
*******************
Response
******************
          Too technical for me; I hope other fire experts chime in.  Thanks for your participation.  The Fire All in One requires installation per code and AHJ approval, or that the subscriber prominently note that the system is not code compliant.  I don’t recommend installing non-compliant fire alarms, even with protective contract provisions. 
*******************

To order up to date Standard Form Alarm /  Security / Fire and related Agreementsclick here:  www.alarmcontracts.com
*************************
CONCIERGE LAWYER SERVICE PROGRAM FOR THE ALARM INDUSTRY
You can check out the program and sign up here: https://www.kirschenbaumesq.com/page/concierge or contact our Program Coordinator Stacy Spector, Esq at 516 747 6700 x 304.
***********************
 
NOTICE:  You can always read our Articles on our website at ww.kirschenbaumesq.com/page/alarm-articles
***********************
THE ALARM EXCHANGEalarm classifieds alarm security contracts

    This area is reserved for alarm classifieds, alarm company announcements, solicitations, offers, etc. 
    There is no charge to post a listing here.Include your contact information, phone, email and web site.  If you would like to submit a post, please send an email to ken@kirschenbaumesq.com.  To create a reciprocal link to our website, click here.

************************************************
Getting on our Email List / Email Articles archived: 
    Many of you are forwarding these emails to friends or asking that others be added to the list.  Sign up for our daily newsletter here: Sign Up.  You can read articles and order alarm contracts on our web site www.alarmcontracts.com
**************************
Ken Kirschenbaum,Esq
Kirschenbaum & Kirschenbaum PC
Attorneys at Law
200 Garden City Plaza
Garden City, NY 11530
516 747 6700 x 301
ken@kirschenbaumesq.com
www.KirschenbaumEsq.com